CostPerCover

Exam Prep app Journeyman Electrician

Practice questions with explained answers

Journeyman electrician practice test

311 practice questions, each with an explanation of why the right answer is right and where the rule comes from. Try 10 of them below; the rest are in the CostPerCover Exam Prep app for iPhone, iPad and Android.

Download on the App Store Get it on Google Play

Free sample of every test. Unlocking the full test is a one-time purchase ($24.99 in the U.S.), with no subscription.

Try 10 questions

Pick your answer first, then open the answer to see why.

Question 1 · Definitions, theory, safety and testing

The safe way to confirm a voltage tester works before a zero-energy check is to:

  1. Test it on the conductor you expect is dead
  2. Test it on a known live source before and after the check
  3. Rely on its self-test light alone
  4. Test it only after the work is done
Show the answer

Answer: B. Test it on a known live source before and after the check

A live-dead-live check proves the tester worked at the moment it read zero.

Source: testing practice (no code lookup)

Question 2 · Services and separately derived systems

Using the optional method, find the calculated load for a 120/240 V dwelling of 2,000 ft² with gas heat and no air conditioning, two small-appliance and one laundry circuit, and nameplate appliances totaling 22,600 VA.

  1. 97.8 A
  2. 68.2 A
  3. 80.2 A
  4. 112.3 A
Show the answer

Answer: C. 80.2 A

General loads: 2,000 ft² × 3 VA (220.41, 2023 NEC) + 2 × 1,500 + 1,500 VA small-appliance and laundry + 22,600 VA of nameplate appliances = 33,100 VA. First 10,000 VA at 100%, the remainder at 40% (220.82(B), 2023 NEC): 19,240 VA. No heating or air-conditioning load is electric, so nothing is added for it. Total 19,240 VA ÷ 240 V = 80.2 A.

Where to find it: Article 220 (Parts I-IV) (optional method, one dwelling)

Source: 220.41, 2023 NEC; 220.52(A), 2023 NEC; 220.52(B), 2023 NEC; 220.82(B), 2023 NEC

Question 3 · Feeders

In the 2023 NEC, where is the rule for this: receptacle outlet load per single or multiple receptacle on one yoke?

  1. 240.4(D)
  2. 220.14(I)
  3. Table 300.5(A)
  4. 220.54
Show the answer

Answer: B. 220.14(I)

Receptacle outlet load per single or multiple receptacle on one yoke is in 220.14(I) (2023 NEC).

Where to find it: Article 220 > 220.14(I)

Source: 220.14(I), 2023 NEC

Question 4 · Branch circuits, overcurrent protection and conductors

Under the 2023 NEC, unless specifically permitted otherwise, what is the maximum overcurrent protection for 14 AWG copper conductors?

  1. 20 A
  2. 10 A
  3. 25 A
  4. 15 A
Show the answer

Answer: D. 15 A

Maximum overcurrent protection, copper 14 AWG (small-conductor rule): 15 A (240.4(D), 2023 NEC).

Where to find it: Article 240 > 240.4(D)

Source: 240.4(D), 2023 NEC

Question 5 · Wiring methods and materials

A metal box will hold 7 insulated 12 AWG conductors entering from outside, 1 device on one yoke, internal cable clamps, and equipment grounding conductors. What is the minimum box volume required?

  1. 24.75 in³
  2. 19.8 in³
  3. 27.84 in³
  4. 22.28 in³
Show the answer

Answer: A. 24.75 in³

Count allowances: 7 conductors + 2 for 1 device yoke (2 each, 314.16(B)(4), 2023 NEC) + 1 for the internal clamps (314.16(B)(2), 2023 NEC) + 1 for all the equipment grounding conductors (314.16(B)(5), 2023 NEC) = 11. Each 12 AWG allowance is 2.25 in³ (Table 314.16(B), 2023 NEC). Required volume = 11 × 2.25 = 24.75 in³.

Where to find it: Article 314 > 314.16(B) counting rules > Table 314.16(B) volume per conductor

Source: 314.16(B)(2), 2023 NEC; 314.16(B)(4), 2023 NEC; 314.16(B)(5), 2023 NEC; Table 314.16(B), 2023 NEC

Question 6 · Equipment and devices

In the 2023 NEC, which article covers luminaires and lampholders?

  1. Article 404
  2. Article 408
  3. Article 410
  4. Article 406
Show the answer

Answer: C. Article 410

Luminaires and lampholders is covered by Article 410 (2023 NEC).

Where to find it: Table of contents > Article 410

Source: Article 410, 2023 NEC

Question 7 · Motors and generators

A motor has a nameplate full-load current of 18.5 A and a marked service factor of 1.15. What is the maximum rating of a separate overload device (basic rule, no adjustment)?

  1. 18.5 A
  2. 23.13 A
  3. 25.9 A
  4. 24.05 A
Show the answer

Answer: B. 23.13 A

Overloads are sized from the NAMEPLATE current, 18.5 A. Service factor 1.15: 125% (430.32(A)(1), 2023 NEC): 18.5 × 125% = 23.1 A.

Where to find it: Article 430 > Part III > 430.32(A)(1)

Source: 430.32(A)(1), 2023 NEC

Question 8 · Special occupancies, equipment and conditions

In the 2023 NEC, which article covers marinas, boatyards and docking facilities?

  1. Article 555
  2. Article 450
  3. Article 600
  4. Article 517
Show the answer

Answer: A. Article 555

Marinas, boatyards and docking facilities is covered by Article 555 (2023 NEC).

Where to find it: Table of contents > Article 555

Source: Article 555, 2023 NEC

Question 9 · Renewable energy and EV charging

An EV charger (EVSE) has a maximum rated load of 32 A. What minimum ampacity must its branch circuit have?

  1. 40 A
  2. 32 A
  3. 36.8 A
  4. 48 A
Show the answer

Answer: A. 40 A

EVSE branch circuit at 125% of the EVSE's maximum load (625.41, 2023 NEC): 32 × 125% = 40 A.

Where to find it: Article 625 > 625.41

Source: 625.41, 2023 NEC

Question 10 · Services and separately derived systems

In the 2023 NEC, where is the rule for this: one-family dwelling service disconnect minimum rating?

  1. 230.79(C)
  2. 110.26(A)(2)
  3. Table 300.5(A)
  4. 210.52(D)
Show the answer

Answer: A. 230.79(C)

One-family dwelling service disconnect minimum rating is in 230.79(C) (2023 NEC).

Where to find it: Article 230 > 230.79(C)

Source: 230.79(C), 2023 NEC

The test at a glance

Journeyman Electrician exam (2023 NEC)

Questions in the app
311
Questions in a practice simulation
80
Time
240 minutes
The app’s practice target
70%
Current to
2023 NEC (NFPA 70)

Topics and their share of the test

Keep practicing in the app

Free sample of every test. Unlocking the full test is a one-time purchase ($24.99 in the U.S.), with no subscription.

Where the questions come from

Independent practice questions. Not affiliated with or endorsed by the National Fire Protection Association (NFPA), NASCLA, PSI, Prov, Pearson VUE or any state licensing board. NFPA 70, National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Inc. This app cites the code; it does not reproduce it. Bring your own copy of the 2023 NEC. The questions are our own practice questions, not questions from the real test.

Other tests in the app